logo
Home > Products > Allen Bradley >
Allen-Bradley 1336-PB-SP5A Common Bus Precharge PCB, 460V, 1336STEF, X40–X60 HP

Allen-Bradley 1336-PB-SP5A Common Bus Precharge PCB, 460V, 1336STEF, X40–X60 HP

Allen-Bradley 1336

X40–X60 HP Range

1336-PB-SP5A datasheet

Place of Origin:

USA

Brand Name:

Allenbradley

Contact Us
Request A Quote
Product Details
Highlight:

Allen-Bradley 1336

,

X40–X60 HP Range

,

1336-PB-SP5A datasheet

Payment & Shipping Terms
Minimum Order Quantity
1
Packaging Details
Brand new and original
Delivery Time
2-3 work days
Payment Terms
T/T
Supply Ability
in Stock
Product Description

AMIKON Industrial Supply · Drive Electronics

Allen-Bradley 1336-PB-SP5A

Common Bus Precharge Printed Circuit Board · 1336STEF Drive Applications


PRECHARGE PCB COMMON BUS (CB) 460 V X40–X60 HP

Product Identification

1336 Series Common Bus Precharge Board

The Allen-Bradley 1336-PB-SP5A is a precharge printed circuit board listed for 460 V 1336STEF common-bus drive applications in the X40–X60 HP range. It is a service component within the drive's precharge system, where controlled DC bus charging is part of drive startup and operation.

CATALOG NUMBER 1336-PB-SP5A

Product Overview

Manufacturer Allen-Bradley
Component Precharge PCB
Bus Arrangement Common Bus (CB)
Drive Designation 1336STEF

Technical Specifications

Catalog Number1336-PB-SP5A
ManufacturerAllen-Bradley / Rockwell Automation
Product TypePrinted Circuit Board
Board FunctionPrecharge
Bus ConfigurationCommon Bus (CB)
Drive Designation1336STEF
Voltage Class460 V
Drive Rating RangeX40–X60 HP
Precharge Board Service Identification
Board Test ConnectorJ1
Board Test FusesF1 / F2
Board Test ResistorsR1, R2, R3, R14, R15, R16
Related Power ComponentPrecharge SCR M1
The board's service identification includes connector J1, fuse positions F1 and F2, resistor test points and its relationship with the precharge SCR circuit. Use the service procedure applicable to the exact drive frame when carrying out component-level checks.

Precharge Function & Drive Application

Role in the DC Bus Charging Process

The precharge circuit supports controlled charging of the drive DC bus before normal inverter operation. The 1336 family troubleshooting information describes precharge completion in relation to stable bus voltage and the operation of the precharge device. In common-bus configurations, the precharge arrangement is part of the drive's shared DC bus operating setup.

Power AppliedDrive input / DC bus supply
PrechargeControlled bus charging
Bus StabilizesVoltage reaches operating condition
Drive ReadyPrecharge sequence completes

Application & Fault Scenarios

Typical System Use

Used as a service spare in the precharge section of supported 460 V 1336STEF common-bus drive installations.

  • Industrial AC drive maintenance.
  • Common-bus drive service and repair.
  • Replacement of a precharge PCB identified during troubleshooting.
  • Maintenance inventory for supported drive configurations.

Why It May Be Searched

  • Drive precharge sequence does not complete.
  • DC bus voltage does not reach the expected stable condition.
  • Inspection identifies a suspected precharge-board fault.
  • Fuse or resistor test results indicate a board-level issue.
  • Maintenance teams need the specified replacement board to restore drive availability.

Production Downtime Consideration

A drive that cannot complete its required precharge sequence may remain unavailable for operation. On equipment dependent on that drive, the resulting interruption can delay machine startup, production recovery or maintenance handover.

Precharge Board Diagnostics

Component Checks Listed in 1336 Troubleshooting Procedures

The 1336 drive troubleshooting procedure for its covered drive variants specifies resistance checks at the precharge board after isolating the drive and disconnecting connector J1.

Test Point Nominal Resistance Reading
Fuse F1 0 Ω
Fuse F2 0 Ω
Resistor R1 80 Ω
Resistor R2 80 Ω
Resistor R3 80 Ω
Resistor R14 80 Ω
Combined resistance of R15 and R16 80 Ω
  • If readings do not match the specified test values, the covered procedure directs replacement of the precharge board.
  • If board readings are correct, inspect wiring and connectors between precharge-board connector J1 and base-driver-board connector J7.
  • Also inspect wiring and connections between the precharge SCR M1 and the precharge board.
Electrical safety: Disconnect and lock out drive power before servicing. Wait for the bus indicator to extinguish and verify zero volts between TB1 terminals +DC and −DC before proceeding. These procedures involve hazardous DC bus circuitry and should be performed by qualified personnel using the correct manual for the installed drive.

The listed resistance values are from the 1336 troubleshooting procedure covering 1336 B040–B050, 1336 C040–C050 and 1336VT B050–B060 drive variants. Confirm that the procedure and board configuration apply to the specific drive being serviced before using these values.

Compatibility & Replacement Checks

Before Selecting the Replacement

  • Match the complete drive catalog number and 1336STEF designation.
  • Confirm the 460 V class and X40–X60 HP application range.
  • Verify that the drive uses the common-bus (CB) configuration.
  • Compare the installed board's catalog number and physical identification.
  • Check the precharge-board connector and associated wiring against the applicable service procedure.
  • Confirm whether the fault is on the precharge board, associated wiring or precharge SCR before replacing components.

Service Documentation

Rockwell Automation · Bulletin 1336 Technical Documentation Publication 1336-PA001 · Spare Parts List Publication 1336-TG001 · Troubleshooting Guide and Renewal Parts Publication 1336-TG002 · Troubleshooting Guide Publication 1336-TG000 · Troubleshooting Guide and Renewal Parts

These publications cover 1336 drive identification, spare-part selection, precharge-board testing, DC bus safety checks and related troubleshooting procedures. Select the procedure according to the installed drive model and frame.

Frequently Asked Questions

01 · Which drive configuration is associated with 1336-PB-SP5A?

It is listed for 460 V 1336STEF common-bus drive applications in the X40–X60 HP range.

02 · What should be checked when the precharge sequence does not complete?

Check the DC bus condition, precharge board, associated connectors and wiring, and the precharge SCR according to the applicable drive troubleshooting procedure.

03 · Which components are included in the documented board resistance test?

The test identifies fuses F1 and F2, resistors R1, R2, R3 and R14, and the combined resistance of R15 and R16.

04 · What should be inspected if the board resistance readings are correct?

Inspect the wiring and connectors between precharge-board connector J1 and base-driver-board connector J7, along with the connections between the precharge SCR and the board.

05 · What information is needed to verify a replacement?

Provide the complete drive catalog number, voltage and horsepower rating, common-bus configuration, existing board label and a clear nameplate or board photograph.

AMIKON industrial automation sourcing and technical supply team INDUSTRIAL SOURCING · TECHNICAL SUPPLY

AMIKON Industrial Supply

Keep Your Maintenance Plan Moving.

From part-number checks to sourcing coordination, AMIKON helps maintenance and purchasing teams move forward with clear product identification and practical supply support.

✉
Miya Zheng · Email sales@amikon.cn
☎
WhatsApp · Direct Inquiry +86 180 2077 6792
Product identification · Availability coordination · Export packaging · Order support

Delivery & Warranty

Pre-dispatch: Part number and available product condition are checked against the order. Packaging is selected for international transport.

Warranty: 12 months, subject to quotation terms and confirmed product condition.

DOA / Returns: Report delivery discrepancies or DOA issues promptly with order details and photos. Returns require prior authorization and are subject to inspection and agreed terms.

Related Models

AMIKON Industrial Supply

Send your inquiry directly to us