logo
Home > Products > Allen Bradley >
Allen-Bradley 1756-OV32E ControlLogix 32-Point DC Electronically Fused Sinking Output Module

Allen-Bradley 1756-OV32E ControlLogix 32-Point DC Electronically Fused Sinking Output Module

32-Point DC Digital Sinking Output

12/24 V DC Output

1756-OV32E datasheet

Place of Origin:

USA

Brand Name:

Allenbradley

Contact Us
Request A Quote
Product Details
Highlight:

32-Point DC Digital Sinking Output

,

12/24 V DC Output

,

1756-OV32E datasheet

Payment & Shipping Terms
Minimum Order Quantity
1
Packaging Details
Brand new and original
Delivery Time
2-3 work days
Payment Terms
T/T
Supply Ability
in Stock
Product Description

AMIKON Industrial Supply

Allen-Bradley 1756-OV32E

INDUSTRIAL CONTROL COMPONENT

The 1756-OV32E provides 32 sinking DC output points arranged in two groups. Its electronically fused output design supports discrete control functions in ControlLogix chassis-based automation systems.

CAT. NO. 1756-OV32E

Module Overview

Designed for DC discrete output applications, the 1756-OV32E switches field-side loads through 32 output channels. Its sinking output architecture provides the electrical interface for compatible DC field devices in a ControlLogix system.

Technical Specifications

MODULE IDENTITY & OUTPUT DESIGN
Manufacturer Allen-Bradley / Rockwell Automation
Product Family ControlLogix
Catalog Number 1756-OV32E
Module Type DC Digital Sinking Output
Number of Outputs 32 points
Output Groups 2 groups, 16 points each
Voltage Category 12/24 V DC sink
Operating Voltage 10–30 V DC
Output Protection Electronic fusing per group
OUTPUT PERFORMANCE
Off-to-On Delay 75 μs nominal 300 μs maximum
On-to-Off Delay 230 μs nominal 1 ms maximum
Off-State Leakage 1 mA per point maximum
On-State Voltage Drop 350 mV DC maximum At 0.5 A
Minimum Load Current 2 mA per output
Surge Current 2 A for 10 ms per point Repeatable every 2 seconds at 60°C
CURRENT & POWER LIMITS
Current per Point 0.5 A at 50°C 0.35 A at 60°C
Current per Group 8 A at 50°C 5 A at 60°C
Current per Module 16 A at 50°C 10 A at 60°C
Backplane Current 390 mA at 5.1 V DC 2 mA at 24 V DC
Backplane Power 2.04 W
Maximum Power Dissipation 5.88 W at 60°C
Thermal Dissipation 20.1 BTU/hr
ISOLATION & INSTALLATION
Isolation Voltage 250 V continuous Outputs-to-backplane and group-to-group
Output Isolation No individual isolation Between outputs within a group
Module Keying Electronic, software configurable
Removable Terminal Block 1756-TBCH / 1756-TBS6H
RTB Keying User-defined mechanical
Slot Width 1 slot
Enclosure Type Open-style; no enclosure
Temperature Code T4
ENVIRONMENTAL CONDITIONS
Operating Temperature 0–60°C 32–140°F
Storage Temperature -40–85°C -40–185°F
Relative Humidity 5–95% Non-condensing
Operating Vibration 2 g at 10–500 Hz
Operating Shock 30 g
Non-operating Shock 50 g
DIAGNOSTIC CHARACTERISTICS
Short-trip Rating 5 A for 20 ms at 24 V DC For output-on then short, and output into short conditions
Diagnostic Timestamp ±1 ms
Fault-mode Output State Hold last state, On or Off Off is the default
Program-mode Output State Hold last state, On or Off Off is the default

Current ratings are temperature dependent. At 60°C, the maximum continuous current is 0.35 A per point, 5 A per group and 10 A per module. Confirm the complete load profile and wiring design against Rockwell Automation technical documentation before commissioning.

Installation & System Integration

Chassis and Terminal Interface

The module is designed for installation in a ControlLogix chassis. The specified removable terminal block options are 1756-TBCH and 1756-TBS6H. Confirm the installed terminal-block type and field wiring arrangement before installation.

Field Wiring Arrangement

Use the manufacturer's wiring diagram for the DC supply and return connections. Follow the terminal assignments and wiring instructions in the module installation documentation.

Configuration Reference

The module uses electronic, software-configurable keying. Verify the selected module identity and configuration in the ControlLogix project before placing the system into operation.

Installation Precaution

Installation, wiring and maintenance should be performed by qualified personnel. Follow the manufacturer's instructions and applicable electrical codes, including relevant hazardous-location precautions.

Application & Fault Scenarios

Typical System Use

The 1756-OV32E is used in ControlLogix systems requiring multiple 10–30 V DC sinking output points. It can switch compatible DC field loads within machine sequencing, equipment interlocks and discrete process-control operations. The connected devices depend on the electrical design of the installation.

Maintenance and Downtime Concerns

Maintenance teams may search for this module when output channels stop switching, a field output becomes unavailable, or a suspected module fault interrupts an output group. If affected outputs control essential machine operations, production sequences may stop while the fault is diagnosed and the module is replaced.

Manufacturer Documentation

The following Rockwell Automation publications provide technical ratings, installation guidance and operating information for the ControlLogix digital I/O family.

1756-TD002 — ControlLogix I/O Modules Specifications Electrical ratings, diagnostic characteristics and environmental specifications.
1756-IN062 — ControlLogix DC Digital I/O Modules Installation requirements, terminal block preparation and wiring guidance.
1756-UM058 — ControlLogix Digital I/O Modules User Manual Module operation, configuration concepts and wiring diagrams.

Frequently Asked Questions

1. What type of module is the Allen-Bradley 1756-OV32E?

It is a ControlLogix 32-point DC sinking output module with electronically fused outputs. Its operating voltage range is 10–30 V DC.

2. How are the 32 output points arranged?

The module has two output groups, each containing 16 points. Electronic fusing is provided per group.

3. What is the maximum continuous output current?

The maximum current per point is 0.5 A at 50°C and 0.35 A at 60°C. Group and module current limits must also be observed.

4. Which removable terminal blocks are specified for the 1756-OV32E?

Rockwell Automation specifies the 1756-TBCH and 1756-TBS6H removable terminal blocks. Confirm the installed terminal block and wiring arrangement before replacement.

5. What should be checked when sourcing a replacement 1756-OV32E?

Confirm the complete catalog number, module condition, terminal-block arrangement, ControlLogix chassis requirements and the electrical ratings of the connected field loads. Compare the existing system configuration with the manufacturer's documentation.

Industrial Automation Parts, Ready When Needed.

AMIKON Industrial Supply supports maintenance teams, system integrators and industrial buyers with sourcing for automation components and hard-to-find spare parts.

Our sourcing process focuses on clear part-number identification, order coordination and practical communication for equipment maintenance and repair requirements.

Allen-Bradley 1756-OV32E ControlLogix 32-Point DC Electronically Fused Sinking Output Module

Contact AMIKON

Contact Miya Zheng for availability, sourcing support and quotation requests.

Sales Contact Miya Zheng
RFQ Information Please include Part Number, Quantity, Destination, Required Date and Machine/System Model when sending your inquiry.

Order & Warranty Support

Inspection & Testing

Product identification and available condition checks are coordinated before dispatch.

Protective Packaging

Items are packed with suitable protective materials for transportation.

Returns & DOA

Report received-item discrepancies or DOA issues with order details and supporting evidence for review.

Warranty

12-month warranty, subject to the agreed quotation terms and applicable conditions.

Send your inquiry directly to us