logo
Home > Products > Allen Bradley >
Allen-Bradley 1746-NIO4I SLC 500 Analog Combination I/O Module

Allen-Bradley 1746-NIO4I SLC 500 Analog Combination I/O Module

SLC 500 Analog I/O Module

2 Differential Analog Input Channels

1746-NIO4I manual

Place of Origin:

USA

Brand Name:

Allenbradley

Contact Us
Request A Quote
Product Details
Highlight:

SLC 500 Analog I/O Module

,

2 Differential Analog Input Channels

,

1746-NIO4I manual

Payment & Shipping Terms
Minimum Order Quantity
1
Packaging Details
Brand new and original
Delivery Time
2-3 work days
Payment Terms
T/T
Supply Ability
in Stock
Product Description
AMIKON Industrial Supply Industrial Automation Parts, Ready When Needed.

Allen-Bradley · SLC 500 Series

1746-NIO4I

Analog Combination I/O Module

Key Product Information

2 Analog Inputs
2 Current Outputs
SLC 500

Discontinued by Rockwell Automation · April 29, 2021

REQUEST A QUOTE

Module Overview

PRODUCT PROFILE

The Allen-Bradley 1746-NIO4I combines analog signal acquisition and current output functions in one module. It is designed for control applications that need to monitor field measurements and issue analog current commands from the same I/O assembly.

Product Lifecycle Rockwell Automation lists catalog number 1746-NIO4I as discontinued effective April 29, 2021.

Technical Specifications

OPEN-BOOK TECHNICAL LAYOUT

Module & Input Data

Catalog Number
1746-NIO4I
Product Family
SLC 500
Module Type
Analog combination I/O
Input Channels
2 differential analog inputs
Output Channels
2 analog current outputs
Input Selection
Voltage or current, selectable per channel
Input Isolation
Input channels are not individually isolated
Mounting
1746 chassis
Terminal Block
Removable
Backplane Current
55 mA at 5V DC; 145 mA at 24V DC
Current Input Range
-20 to +20 mA
Voltage Input Range
-10 to +10V DC, minus 1 LSB at upper limit
Current Input Impedance
250 Ohms
Voltage Input Impedance
1 MOhm
Current Input Resolution
1.22070 µA per LSB
Voltage Input Resolution
305.176 µV per LSB
Current Input Full Scale
20 mA
Input Configuration
Voltage/current selection by module DIP switches

Current Output Data

Output Range
0 to +20 mA
Converter Resolution
14 bit
Output Resolution
2.56348 µA per LSB
Full Scale
21 mA
Overrange Capability
5%, up to 21 mA minus 1 LSB
Load Range
0 to 500 Ohms
Maximum Load Reactance
100 µH
Step Response
2.5 ms at 95%
Non-linearity
0.05%
Conversion Method
R-2R ladder
Accuracy at +25°C
±0.298% of full scale, maximum
Accuracy at 0 to +60°C
±0.541% of full scale, maximum

Verify the module series, channel selection, wiring arrangement and application requirements against the installed system documentation before commissioning.

Application & Fault Scenarios

SYSTEM CONTEXT

Application Environment

Used in SLC 500 control systems where analog field signals must be monitored and current output commands delivered to connected process equipment. Typical tasks include acquiring process measurements and sending analog control references.

Maintenance & Downtime Risk

Maintenance teams may search for this module when analog readings become unstable, input channels stop updating, current outputs fail to respond, or the installed unit is damaged. Loss of these signals can interrupt process monitoring or control and contribute to equipment downtime.

Installation & Verification

FIELD CONSIDERATIONS

Before installation, confirm the catalog number, module revision, chassis arrangement and channel configuration. Check the voltage/current selection switches and verify terminal assignments against the applicable Rockwell Automation installation instructions.

Use suitable shielded wiring and grounding practices for analog signals. Before removing or installing the module or terminal block, follow the system's approved isolation and electrical safety procedures.

For replacement, compare the existing wiring, input signal type, output load and controller configuration rather than relying on the catalog number alone.

Frequently Asked Questions

1746-NIO4I FAQ
1. Can the input channels accept both voltage and current signals?

Yes. Each input channel can be configured for voltage or current using the module's DIP switches. Check the selected signal type and wiring before operation.

2. What current signal does the output section provide?

The module provides two analog current outputs with a normal operating range of 0 to +20 mA.

3. Is the 1746-NIO4I still manufactured by Rockwell Automation?

No. Rockwell Automation lists this catalog number as discontinued effective April 29, 2021. Availability should be confirmed before placing an order.

4. Which information should be checked before ordering a replacement?

Confirm the full catalog number, module revision, installed chassis, field signal types, wiring and the existing control-system configuration.

Related Models

ADDITIONAL PART REFERENCES

AMIKON Industrial Supply

INDUSTRIAL PARTS SOURCING & SUPPORT

Industrial Automation Parts, Ready When Needed.

AMIKON supports industrial parts sourcing for automation maintenance, equipment repair and spare-parts procurement, with order communication focused on the details that matter to your application.

  • Part-number and order-detail confirmation
  • Pre-dispatch condition checks as applicable to the quoted item
  • Protective packaging for shipment
  • DOA and return requests reviewed under agreed order terms
  • 12-month warranty, subject to quotation and warranty terms
Sales Contact Miya Zheng
RFQ Information: Please include Part Number, Quantity, Destination, Required Date and Machine/System Model. Testing, packaging, DOA handling, returns and warranty are subject to the agreed quotation and order terms.

Send your inquiry directly to us