9563-810

Other Videos
December 08, 2025
Category Connection: Triconex
Brief: Experience a brief tour of features designed to deliver dependable outcomes. In this video, we showcase the Triconex 9563-810 Digital Input Termination Panel, demonstrating its installation, wiring configuration, and how it provides critical isolation and protection for industrial control systems. You'll see how this panel integrates with 32-point digital input modules and learn about its application in safety-critical environments like emergency shutdown systems.
Related Product Features:
  • Provides 16 digital input points with commoned 24V DC power terminals (PWR+ and PWR-) for efficient field device connection.
  • Features ≥1500VAC field-to-system isolation to protect backplane and main processors from field surges and electrical noise.
  • Includes individual fuse protection with blown-fuse indicators for each input point, enhancing safety and simplifying maintenance.
  • Designed for compatibility with Triconex 32-point digital input modules, requiring two panels per module for full functionality.
  • Supports Triple Modular Redundant (TMR) input modules, ensuring signal reliability even if one signal path fails.
  • Includes dual labeling sets (1-16 and 17-32) for easy identification and correct installation across multiple panels.
  • Simplifies power distribution to field switches and sensors with commoned power terminals for streamlined wiring.
  • Ideal for critical applications including emergency shutdown systems, valve position feedback, and turbine control monitoring.
FAQs:
  • How many input points does the 9563-810 Termination Panel support?
    The 9563-810 provides 16 digital input points with commoned power terminals. When used with 32-point digital input modules, two termination panels are required for complete system functionality.
  • What level of electrical isolation does this termination panel provide?
    This panel offers ≥1500VAC field-to-system isolation, which prevents field surges from reaching the backplane and damaging main processors, along with ≥250VAC channel-to-channel isolation for enhanced system protection.
  • What safety features are included for maintenance and protection?
    Each of the 16 input points includes individual fuse protection with a blown-fuse indicator, allowing for quick identification of issues and enhanced safety during maintenance operations.
  • Is this termination panel compatible with Triple Modular Redundant systems?
    Yes, the 9563-810 is specifically designed for compatibility with Triconex Triple Modular Redundant (TMR) input modules, ensuring signal reliability continues even if one signal path experiences a failure.