logo
Home > Products > ICS Triplex >
ICS Triple T8451C Conformal-coated 24 VDC Digital Output Module for Safety-critical Control

ICS Triple T8451C Conformal-coated 24 VDC Digital Output Module for Safety-critical Control

ICS Triple T8451C

T8451C DOM

T8451C datasheet

Place of Origin:

UK

Brand Name:

ICS Triple

Model Number:

T8451C

Contact Us
Request A Quote
Product Details
Highlight:

ICS Triple T8451C

,

T8451C DOM

,

T8451C datasheet

Payment & Shipping Terms
Minimum Order Quantity
1
Packaging Details
Brand new and original
Delivery Time
2-3 work days
Payment Terms
T/T
Supply Ability
in Stock
Product Description
ICS Triplex T8451C Trusted TMR digital output module


TRUSTED TMR OUTPUT
T8451C
Coat 24 VDC Digital Output Module
40 channels engineered as five isolated power groups for safety-related final elements.
40
OUTPUTS
2 A
PER CHANNEL
1 ms
SOE RESOLUTION
Confirm Series C, firmware, slot and termination before purchase.
Sales Manager: Miya Zheng   Email Inquiry   WhatsApp

◇How T8451C Fits the Safety Loop
◉ TRUSTED TMR OUTPUT STAGE
Triplicated control for 40 final elements
The ICS Triplex T8451C is a conformal-coated 24 VDC digital output module for safety-critical control. Triplicated processing and hardware voting supervise each output path while automatic diagnostics and field-line monitoring reveal faults without sacrificing the commanded state.
Five independent groups
Eight channels per group simplify field-power segregation and current planning.
➔ COMMAND
Voted output demand from the Trusted system.
◎ MONITOR
Channel diagnostics, line status and current supervision.
✓ VERIFY BEFORE ORDER
Series C, firmware, slot, termination and replacement method.
Signal path: TMR command  →  voted channel  →  monitored 24 VDC field load
⚙Technical Specifications
T8451C TRUSTED OUTPUT DATA
Circuit Type Fully triplicated TMR Outputs 40 channels
Power Groups 5 groups of 8 Field Voltage 18-32 VDC
System Supply 20-32 VDC Continuous Current 2 A per channel
Group Limit 8 A per group Minimum On Load 50 mA
Turn On/Off Delay 0.5 ms SOE Resolution 1 ms
Self-Test Interval 2 minutes Short Circuit Electronic latching
Operating Range -5 to +60 C Humidity 5-95%, non-condensing
Dimensions 241 x 30 x 300 mm Weight 1.13 kg
⇄System Integration
TMR PROCESSOR
Voted output commands
T8451C
40 triplicated outputs
FIELD LOADS
Valves, relays and solenoids
Install in a T8100 or T8300 Trusted I/O slot, match the field termination and five power-group supplies, and plan Companion Slot or SmartSlot access for online replacement.
Features & Applications
TMR FAULT TOLERANCE
Triplicated channels and hardware voting sustain safe output control.
LINE MONITORING
Open and short circuit detection supports field-loop diagnostics.
SAFETY DUTIES
ESD, fire and gas, burner management and critical process trips.
✓AMIKON Supply Service
Fast, Reliable Industrial Parts Delivery
AMIKON supplies quality new and discontinued automation parts with efficient sourcing, dependable delivery and service built for long-term cooperation.
QUALITY INSPECTION WAREHOUSE NETWORK
12 Months
WARRANTY
Return Support
Contact us within seven days if a concern arises. Items should remain in original condition with a clear return reason. Refund or replacement follows receipt and inspection; return freight is paid by the buyer.
Sales Manager: Miya Zheng   |   sales@amikon.cn   |   WhatsApp: 86-18020776792
T8451C Buying Decisions
01 / VARIANT
Can ICS Triplex T8451C replace T8451 without engineering changes?
Do not approve substitution from the model name alone. T8451C denotes the conformal-coated Series C build. Match the installed module's complete label, Trusted system release, firmware, slot keying and field termination. A mismatch can prevent recognition or alter the approved safety configuration.
02 / LOAD STUDY
Is ICS Triplex T8451C suitable for our solenoids and relays?
Check four values for every load: normal current below 2 A, combined current below 8 A in each eight-channel group, on-state current at least 50 mA, and inrush within the field circuit capability. Inductive loads also need the correct suppression arrangement; steady-state current alone is not enough.
03 / SLOT PLAN
What must be confirmed before an online ICS Triplex T8451C changeout?
Verify whether the chassis uses a dedicated Companion Slot or a SmartSlot replacement path, confirm the healthy module state, maintenance override procedure and field power segregation, then follow the site's approved safety procedure. Never assume that an adjacent empty slot is configured for replacement.
04 / ACCEPTANCE
Which tests add value when buying an ICS Triplex T8451C spare?
Request label and coating-condition photos plus connector inspection. Functional acceptance should cover power-up diagnostics, all 40 channel commands, voltage/current readback, line monitoring, group supply behavior and latching short-circuit protection. A simple power-on photo does not prove output health.
05 / RFQ DATA
What should an ICS Triplex T8451C purchase request contain?
Include quantity, exact label photos, Series and serial/date code, firmware or system-release constraint, T8100/T8300 chassis details, termination assembly, Companion Slot or SmartSlot method, required condition, destination and required delivery date. These details prevent avoidable compatibility returns.
Need ICS Triplex T8451C?
Send the Series, firmware preference, quantity, termination details and destination for availability confirmation.
Sales Manager: Miya Zheng   |   Email Inquiry WhatsApp