logo
Home > Products > Vibro Meter >
VIBRO METER VM600 MPC4 200-510-070-113 Machinery Protection Card with 4 Dynamic Signal Inputs

VIBRO METER VM600 MPC4 200-510-070-113 Machinery Protection Card with 4 Dynamic Signal Inputs

4 Dynamic Signal Inputs MPC4 Card

2 Speed Inputs Machinery Protection Card

60 kHz Analog Frequency Range Vibration Monitoring Card

Place of Origin:

USA

Brand Name:

VIBRO METER

Model Number:

VM600 MPC4 200-510-070-113

Contact Us
Request A Quote
Product Details
Place Of Shipment:
Xiamen, China
LP/HP Ratio In Pass Band:
500 Max.
Ripple:
±0.3 DB
Slope:
6 To 60 DB/octave (software Configurable)
Attenuation Outside Pass Band:
>50 DB
Amplitude Accuracy:
±1% Of Full-scale
Linearity Error:
<±1%
Equivalent Input Noise(without Integration):
<200 µV RMS
Highlight:

4 Dynamic Signal Inputs MPC4 Card

,

2 Speed Inputs Machinery Protection Card

,

60 kHz Analog Frequency Range Vibration Monitoring Card

Payment & Shipping Terms
Minimum Order Quantity
1
Price
66USD
Packaging Details
Brand new and original
Delivery Time
2-3 work days
Payment Terms
T/T
Supply Ability
in stock
Product Description
VIBRO METER VM600 MPC4 200-510-070-113 Machinery Protection Card
VIBRO METER VM600 MPC4 200-510-070-113 Machinery Protection Card with 4 Dynamic Signal Inputs 0
This versatile machinery protection card is capable of measuring and monitoring up to four dynamic signal inputs and up to two speed inputs simultaneously. The dynamic signal inputs are fully programmable and can accept signals representing acceleration, velocity, displacement (proximity), and other physical parameters.
On-board multi-channel processing allows measurement of relative and absolute vibration, Smax, eccentricity, thrust position, absolute and differential housing expansion, displacement, and dynamic pressure. Digital processing functions include digital filtering, integration or differentiation, rectification (RMS, mean value, true peak, or true peak-to-peak), order tracking (amplitude and phase), and measurement of the sensor-target gap.
The speed (tachometer) inputs accept signals from a variety of speed sensors, including proximity probes, magnetic pulse pick-up sensors, or TTL signals, with support for fractional tachometer ratios. Configuration can be expressed in metric or imperial units, with fully programmable Alert and Danger set points, as well as alarm time delay, hysteresis, and latching. The Alert and Danger levels can also be adapted according to speed or external information.
Each alarm level provides a digital output internally via the corresponding IOC4T input/output card, which can drive four local relays on the IOC4T or be routed via the VM600 rack's Raw bus or Open Collector (OC) bus to optional relay cards such as the RLC16 or IRC4. The processed dynamic and speed signals are also available as analog output signals on the rear of the rack (front panel of the IOC4T), in both voltage-based (0-10 V) and current-based (4-20 mA) formats.
Self-Testing & Diagnostics
The MPC4 performs a self-test and diagnostic routine on power-up, and its built-in "OK system" continuously monitors the level of signals from the measurement chain (sensor or signal conditioner), indicating any broken transmission line, faulty sensor, or signal conditioner. An LED on the MPC4 front panel indicates whether a processing or hardware error has occurred, while six additional LEDs (one per input channel) show whether the OK System has detected a fault or an alarm on the channel.
The MPC4 card is available in three versions: a standard version, a separate circuits version, and a safety (SIL) version, all of which operate as a card pair with the corresponding IOC4T input/output card.
VIBRO METER VM600 MPC4 200-510-070-113 Machinery Protection Card with 4 Dynamic Signal Inputs 1
Technical Specifications
Number of inputs 4 per MPC4 card
DC range 0 to +20 V or 0 to −20 V
AC range ±10 V max.
Common mode voltage range −50 to +50 V
CMRR >60 dB at 50 Hz
Crosstalk −72 dB
Input impedance 200 kΩ
Current input range (DC signals) 0 to 25 mA
Current input range (AC signals) ±8 mA max.
Analog frequency range DC to 60 kHz (−3 dB)
VIBRO METER VM600 MPC4 200-510-070-113 Machinery Protection Card with 4 Dynamic Signal Inputs 2
Key Features
  • Continuous Online Protection: Always-on machinery monitoring for maximum reliability
  • Advanced Real-Time DSP: High-precision measurement and processing of dynamic signals
  • Multi-Channel Capability: 4 dynamic signal channels and 2 tachometer (speed) channels, all individually programmable
  • Flexible Filtering: Programmable broad-band and narrow-band filters for precise signal analysis
  • Order-Tracking Mode: Simultaneous amplitude and phase monitoring
  • Adaptive Safety Levels: Fully programmable Alert, Danger, and OK set points, with adaptive Alert and Danger thresholds
  • Sensor Connectivity: Integrated power supplies for IEPE accelerometers and proximity measurement systems
  • Front-Panel Access: BNC connectors for easy analysis of buffered "raw" sensor signals
  • LED Indicators: Front-panel LEDs display status, OK, and alarm conditions
  • Hot-Swappable Design: Live insertion and removal of cards without system downtime
  • Flexible Versions: Available in Standard, Separate Circuits, and Safety (SIL) versions to suit different safety and redundancy requirements
VIBRO METER VM600 MPC4 200-510-070-113 Machinery Protection Card with 4 Dynamic Signal Inputs 3
Company Commitment
As a global B2B leader, Amikon is committed to speed and precision. We strive to be the Gold Standard of the industry with our exceptional service and support.
Our Service Promise
  • Fast Quotes: You get a reply in approximately 30 minutes
  • Fast Shipping: We ship in 1-2 business days
  • Real Support: Personal attention to ensure complete satisfaction
Quick Specifications
Warranty: 1 Year (12 Months)
Shipping: DHL / UPS / TNT / FedEx / EMS
Payment: T/T
Documentation: Data sheets and manuals available upon request
Ready to Get a Quote?
Miya Zheng
Sales Manager @ Amikon
Mobile: +86 180 2077 6792
Email: sales@amikon.cn