logo
Home > Products > Allen Bradley >
Allen-Bradley 1503VC-BMC4 IntelliVAC Contactor Control Module – Series C / D

Allen-Bradley 1503VC-BMC4 IntelliVAC Contactor Control Module – Series C / D

IntelliVAC Contactor Control Module

Series C / D Control Module

Allen-Bradley 1503VC-BMC4 pdf

Place of Origin:

USA

Brand Name:

Allenbradley

Contact Us
Request A Quote
Product Details
Highlight:

IntelliVAC Contactor Control Module

,

Series C / D Control Module

,

Allen-Bradley 1503VC-BMC4 pdf

Payment & Shipping Terms
Minimum Order Quantity
1
Packaging Details
Brand new and original
Delivery Time
2-3 work days
Payment Terms
T/T
Supply Ability
in Stock
Product Description


Allen-Bradley · Bulletin 1503VC · IntelliVAC
1503VC-BMC4
IntelliVAC Contactor Control Module
Series C / D Medium Voltage Control Bulletin 1502
Request a Quote  →
01 / PRODUCT
Product Role

IntelliVAC control for medium-voltage vacuum contactors

The 1503VC IntelliVAC control module operates Bulletin 1502 vacuum contactors used in medium-voltage motor starter and feeder applications. The Series C / D version supports both electrically held and mechanically latched contactor types.

Rockwell Automation identifies 1503VC-BMC4 as the spare-part number for the electrically held and mechanically latched Series C and D module.

02 / APPLICATION
System Use

Where this module is used

Installed in the low-voltage control section of medium-voltage motor controllers, including Rockwell Automation Bulletin 1500/1900 CENTERLINE equipment. It interfaces with Bulletin 1502 vacuum contactors.

Typical sourcing situations

Customers may search for this module when a contactor fails to energize, fails to close or open, drops out during operation, or reports a module fault. These symptoms can also involve control power, fuses, wiring, contactor coils, auxiliary feedback or configuration—not necessarily a failed IntelliVAC module.

If the contactor control circuit cannot operate correctly, the associated motor starter or feeder may be unavailable, potentially interrupting the driven process.

03 / SPECIFICATIONS
Technical Data

Manufacturer-documented Series C / D specifications.

Electrical Ratings
Parameter Rating
Main AC supply 110–240 V AC RMS, +10% / -15%, 47–63 Hz
Main DC supply 110–250 V DC, +10% / -15%
Maximum idle current, AC 125 mA
Maximum idle current, DC 35 mA
Maximum hold current, AC 300 mA
Maximum hold current, DC 100 mA
Command input voltage 100–240 V AC RMS / 50–250 V DC
Maximum command input on-state current 9 mA AC / 9 mA DC at 250 V
Status output contacts 250 V AC RMS, 5 A resistive / 2 A reactive; 30 V DC, 5 A resistive / 2 A reactive
Internal control fuse 6.3 A, 250 V; Littlefuse 21506.3
Command input ratings and contact ratings must be checked against the connected control circuit and application.
Mechanical & Environmental Ratings
Parameter Rating
Operating temperature 0 to 60°C ambient at control module
Storage temperature -40 to 85°C
Altitude -1,000 to 5,000 m
Humidity 95% non-condensing
Pollution level Pollution Degree 2
Operational shock 15 g peak, 11 ms
Operational vibration 10–57 Hz: 0.015 in peak-to-peak; 57–150 Hz: 2.5 g
Dimensions Approx. 185.3 × 165.9 × 59.4 mm (drawing dimensions)
Mounting Two mounting screws
Operating temperature is derated at altitudes above 1,000 m. Refer to the manufacturer manual for the altitude-specific limits.
04 / CONFIGURATION
Series & Firmware

The module is configured by DIP switches located inside the enclosure. The firmware version is displayed above the DIP switches.

Series-specific firmware
  • Series C: application firmware version 2.003.
  • Series D: application firmware version 3.001 or 3.002.
  • Series D firmware is not compatible with other series-letter modules.

Confirm the series letter on the module label before ordering or replacing the unit. Series C and D are distinct configurations even though both use the 1503VC-BMC4 spare-part number.

05 / INSTALLATION
Mounting & Interface

  • Typically mounted in the low-voltage control panel of a medium-voltage controller.
  • Uses two mounting screws.
  • Interfaces with Bulletin 1502 vacuum contactors through quick connectors and a wiring harness.
  • Control power and other control-circuit connections also use quick connectors.
  • For OEM mounting, the manual recommends at least 38.1 mm free air space above and below the module.
Installation, wiring and commissioning should be performed by suitably trained personnel following the applicable electrical codes and the manufacturer's instructions.
06 / DIAGNOSTICS
Status Checks

The module provides separate Module Status and Contactor Status LED indications, together with corresponding status relay outputs.

Observed condition Checks indicated in the manual
Contactor does not energize Check control power, control-circuit connections, power input plug and internal fuse.
Contactor fails to close Check coil condition, loose connections, auxiliary contact adjustment and mechanical obstruction.
Contactor drops out during operation Check motor protection, stop command, control voltage, TDUV conditions and contactor status feedback.
Module fault indication Check DIP switch configuration and control power; follow the Series C or Series D LED status table.

A fault indication does not by itself establish that the module is defective. Follow the Series C / D troubleshooting procedure before replacement.

07 / SUPPLY
Delivery & Support

AMIKON Industrial Supply

We support industrial spare-parts sourcing with order verification and practical shipment coordination.

Before dispatch
Part-number and condition checks as applicable.
Packaging
Protective packing for international shipment.
DOA / Returns
Report transit damage or DOA promptly with photos; returns require prior authorization.

Warranty: 12 months, subject to the terms stated in the quotation. Coverage and supplied condition are confirmed per order.


AMIKON INDUSTRIAL SUPPLY
Industrial Sourcing, Built Around Your Requirements.

AMIKON helps maintenance teams, purchasing departments and industrial service providers source control components and automation spare parts. Share the complete part number and equipment details to help us check your request accurately.

CONTACT PERSON
Miya Zheng


AMIKON industrial parts sourcing and service team
INDUSTRIAL PARTS · GLOBAL SOURCING
Request a Quotation

Please include the following details for a more accurate quotation:

Part Number Quantity Destination Required Date Machine/System Model
PRODUCT QUESTIONS
Frequently Asked Questions
1. What is the difference between 1503VC-BMC4 Series C and Series D?

Both are identified by Rockwell Automation under the BMC4 spare-part number. Series D includes firmware enhancements related mainly to fault and warning handling. Series C uses firmware 2.003; Series D uses 3.001 or 3.002, which is not compatible with other series-letter modules.

2. Which contactors can the IntelliVAC control?

The Series C / D IntelliVAC is documented for Bulletin 1502 medium-voltage vacuum contactors, including 400 A and 800 A ratings, with electrically held and mechanically latched arrangements.

3. How is the module configured?

Configuration is performed using DIP switches located inside the enclosure. The correct settings depend on the contactor and application; refer to the Series C / D user manual.

4. What should be checked if the contactor does not close?

The manufacturer troubleshooting guide identifies possible checks including control power, the internal fuse, coil condition, loose connections, auxiliary contact adjustment and mechanical obstruction. A module replacement should follow diagnosis.

5. What information should be confirmed before ordering?

Confirm the full catalog number, Series C or D label, installed contactor type and rating, control supply, and the existing configuration. These details help reduce replacement mismatches.

Related Models & Industrial Parts References

Additional part numbers from the supplied sourcing list. These are reference items only and do not indicate compatibility or interchangeability with this product.

Model / Reference Model / Reference Model / Reference
X20DO4529 OFI-3 Siemens 6ES5440-8MA22
MCR-SL-PT100-LP-NC X20TB1E HACH 2100P
8BVI0028HWS0.000-1 Cisco 4G-AE010-R X20D02623
TF65-40 1SAZ811201R1003 AB6203-B HID 70200AEP0N
X67BCE321.L12 ABB DI810 3BSE008508R1 ET1212PPH-S-DR
BWU2234 AB7006-B DAWE D-1422C
Siemens AQR2531ANW 7XV116.50-51 ABB BT2 3N-40-320-P 2TAM103100R4500
HACH 2612602 X20TB5F 175G5122 SKKT92/16
PR 2261 4PP065.0571-X74 Honeywell XF521
IB IL RS232 X20TB32 Conzerv EM6400
DI524 1SAP240000R0001 Norgren F72G-3AS-001 MQSPS-DH-1-30
DAWE D-1422C X20DO2623 Cisco 07-1144-01
Flender Loher 0220401 ER40 82120AKI000 Telemecanique LR2D1321
AC123 BWU2192 7DM465.76
AB7694-F 8AC120.60-1 3IF787.9-1
HACH PHC281 FSM500 K/T(E) Allen-Bradley 889D-F4AC-2
Looking for 1503VC-BMC4 manual information or an IntelliVAC Series C / D replacement? Contact AMIKON with the complete module label, series identification and application details for sourcing assistance.
AMIKON Industrial Supply · Industrial Automation Spare Parts Sourcing

Send your inquiry directly to us