The 330104 family combines an 8 mm sensing tip, M10×1 case thread and armored cable construction. It senses the gap to a conductive machine target without physical contact.
◆ System boundary The probe works with a compatible extension cable and Proximitor Sensor. These components form one calibrated measurement chain.
⚠ Replacement control: use the complete `330104-00-06-10-02-00` identity and compare the installed probe geometry directly. A shared 330104 prefix does not establish interchangeability.
02 / BUILD PROFILE
Confirmed construction
⚙
■ Product identity 330104-00-06-10-02-00
◎ Probe family 3300 XL 8 mm
⚙ Case thread M10×1
⇄ Cable form Armored
◉ Tip diameter 8.0 mm
✓ Chain role Probe + extension + Proximitor
03 / INSTALLATION ROUTE
Four controls before loop acceptance
⚙
THREAD FIT
Confirm M10×1
→
⇅
GAP
Capture installed position
→
⇄
ARMOR
Protect bend and strain
→
✓
CHAIN TEST
Prove signal and scale
ⓘ Verify mechanical gap, direction, usable span, stable output, noise level, connector security and monitor scaling before restoring protection.
◆ AMIKON / SINCE 2005
Exact spares for critical industrial systems.
Amikon supplies PLC, HMI, DCS, industrial PC, drive and machinery-monitoring spares worldwide. Experienced teams help resolve difficult part numbers and complex replacement needs so production can keep moving.
↻ Return support: Contact us within 7 days if an issue is found. Keep the item in original condition and state the return reason. Return or replacement follows receipt and inspection; shipping costs remain with the buyer.
04 / FIELD DECISIONS
330104-00-06-10-02-00 FAQ
⇄
Can 330104-00-06-10-02-00 replace a 330103 probe? Not automatically. Both use M10×1 threads, but 330104 has armored cable while 330103 does not. The complete suffix and geometry must also match.
⇅
What should be captured before removing 330104-00-06-10-02-00? Record the full code, probe position, mechanical gap, thread engagement, lead routing, connector, extension cable, Proximitor Sensor and monitor scale.
⚠
Why can 330104-00-06-10-02-00 show a shifted gap voltage? Target material, physical gap, nearby metal, a mismatched chain, connector condition and cable routing can alter the result.
⚙
How should the 330104-00-06-10-02-00 armor be routed? Avoid crushing, tight bends, unsupported vibration and contact that can abrade the armor or transfer strain to the probe.
✓
How should 330104-00-06-10-02-00 be accepted? Verify thread fit, mechanical gap, movement direction, usable span, stable output, low noise, secure connections and correct protection scaling.