logo
Home > Products > Bently Nevada >
Bently Nevada 330195-02-12-05-05 Extended Temperature Range (ETR) Reverse Mount Proximity Probe

Bently Nevada 330195-02-12-05-05 Extended Temperature Range (ETR) Reverse Mount Proximity Probe

Bently Nevada 330195-02-12-05-05

330195-02-12-05-05 3300 XL 8 mm

330195-02-12-05-05 Reverse Mount

Place of Origin:

USA

Brand Name:

Bently Nevada

Model Number:

330195-02-12-05-05

Contact Us
Request A Quote
Product Details
Highlight:

Bently Nevada 330195-02-12-05-05

,

330195-02-12-05-05 3300 XL 8 mm

,

330195-02-12-05-05 Reverse Mount

Payment & Shipping Terms
Minimum Order Quantity
1
Packaging Details
Brand new and original
Delivery Time
2-3 work days
Payment Terms
T/T
Supply Ability
in Stock
Product Description
EXTENDED TEMPERATURE RANGE
330195-02-12-05-05
3300 XL 8 mm reverse-mount proximity probe
⚙ 3/8-24 UNF⇄ 0.5 m✓ Approval 05
↺
Reverse Mount
Designed for rear-access or sleeve-based probe installation where forward adjustment is not the preferred arrangement.
Confirm ETR loop compatibility before release
Sales Manager: Miya Zheng
✉ EMAIL ☎ WHATSAPP
◎
ETR sensing for difficult machine locations
01 / FUNCTION
Non-contact shaft measurement
The probe is part of a 3300 XL 8 mm transducer system that converts the gap between the probe tip and a conductive target into a proportional voltage. The signal supports radial vibration, axial position, phase timing and speed-related measurements.
↺ Reverse-access geometry
Useful where adjustment or removal must occur from the rear side.
☀ ETR construction
Chosen for higher-temperature probe and cable environments.
02 / ORDERING IDENTITY
What the Complete Number Confirms
01
Probe type
330195 extended-temperature-range reverse-mount probe ◎ Tip diameter
8.0 mm
02
Mounting form
Reverse mount; 3/8-24 UNF-2A thread ⚙ Fixed geometry
02-12 ordering arrangement
03
Total length
05 = 0.5 metre (1.6 feet) ⇄ Cable
75 ohm integral probe cable
04
Approval
05 = CSA, ATEX and IECEx approval option ✓ Loop family
3300 XL 8 mm system
Important: ETR components can operate with the standard 3300 XL Proximitor Sensor, but a loop containing an ETR component is evaluated to the ETR system performance limits.
⇄ Build the Measurement Loop in the Right Order
◎
1 · Target
Conductive shaft surface
➜
↺
2 · Probe
330195 reverse mount
➜
⇄
3 · Cable
Correct ETR/system length
➜
⚙
4 · Proximitor
Compatible 3300 XL sensor
Mechanical review
Rear access, thread engagement, sleeve arrangement and tip clearance.
Electrical review
System length, connector condition, grounding and monitor input.
Commissioning review
Initial gap voltage, runout, polarity and alarm logic.
AMIKON · GLOBAL AUTOMATION SUPPLY
Two decades of hard-to-find parts sourcing
Founded in Hong Kong in 2005, Amikon supports industrial maintenance teams with PLC, HMI, DCS, industrial PC and VFD spare parts. Experienced sales and service teams help identify difficult part numbers, coordinate urgent dispatch and keep production plans moving.
⚡ Rapid response✓ 12-month warranty
↻
Return path
Report concerns within seven days. Returned goods must remain in their original condition with a clear reason. A return or replacement is arranged after receipt and inspection; return freight is the buyer's responsibility.
Sales Manager: Miya Zheng   ·   sales@amikon.cn   ·   WhatsApp: 86-18020776792
DECISION SUPPORT
FAQ for 330195-02-12-05-05
01
?
Why should 330195-02-12-05-05 not be replaced by a standard-temperature reverse-mount probe?
The ETR version is selected for a different temperature envelope. A substitution can change permissible probe/cable exposure and overall loop accuracy.
02
?
Can 330195-02-12-05-05 be used with a standard 3300 XL Proximitor Sensor?
Yes, ETR probe components can be used with the standard sensor, but the complete loop follows ETR system performance limits.
03
?
What mounting detail is most often missed for 330195-02-12-05-05?
It is a reverse-mount probe. Confirm rear-access space, sleeve or bracket geometry, 3/8-24 UNF engagement and the adjustment method before ordering.
04
?
Does the 0.5 m length of 330195-02-12-05-05 define the entire transducer system?
No. It is the probe's integral length. The extension cable and Proximitor Sensor must still be selected to create the required total system length.
05
?
What should be verified when buying 330195-02-12-05-05 as an installed spare?
Confirm the exact full number, hazardous-area approval, reverse-mount hardware, existing extension cable, Proximitor model, total electrical length and target material. These checks prevent a mechanically similar but electrically incorrect replacement.
☷ Recommended Models
3500/22 146031-01 AL-RS4 4AO R-Myra-300-P MS-2000H-BT
SDV531-L63/PRP 80438SE 417785 SLP8-2-M RAYSTAT-EX-03
644HAE5Q4M5J6QTCN 599405976740 AVM234SF132 BB-MESR922T
1008041100.0400 SPARK200 253G-200E-29 NI9205 / 199015A-01L
TS-0524-WR 2711P-K4M20D8 51305406-100 CKCD0232-EU
W3000 PCO3CT0GL0 S82G-1024 MM300-BEHP1CAEXXX ID-800
DPT200-101 CC-PCNT02 HW-300 64-825-0146-01 V1
TRX-200S A2BN5D-221D0 NTB-HD-RTL1-SW-R4 131B0514
ESP-00 359843-0020 X435-8P-4S OM70BHONDT 1MRK000614ABr04
644HFI5Q4M5J6 S-014591-02 RCF ZX 8060 XP50-TTA/DC
◎ ⇄ ⚙
Confirm mounting, temperature and loop length together
Send the installed probe number, sensor model, cable arrangement and required delivery date.
Sales Manager: Miya Zheng   ·   ✉ sales@amikon.cn   ·   ☎ 86-18020776792

Send your inquiry directly to us