The 1756-PB72 converts its supplied DC input into the backplane power rails used by compatible ControlLogix chassis modules.
Before sourcing a replacement, confirm the installed catalog number, chassis type, input supply and required backplane capacity.
Install the supply at the left end of a compatible ControlLogix chassis. Its connector mates directly with the backplane; make sure the unit is correctly seated and the chassis assembly is secure.
Use a 24V DC source within the 19–32V DC operating range. Isolate power first, identify positive and negative conductors, connect to the corresponding input terminals and verify polarity before energizing.
Use solid or stranded copper conductors rated for at least 90°C, sized at 14 AWG (2.5 mm²), within the specified insulation limits. Terminal torque is 0.565 N·m (5 lb-in); avoid overtightening.
Confirm chassis and module compatibility, input polarity, terminal connections and supply voltage before restoring power. Follow site electrical safety procedures and keep the equipment within its rated environment.
Typical sourcing situations include chassis power loss, a rack that will not power up, suspected power-supply failure, or planned maintenance requiring an exact catalog-number replacement.
An interrupted chassis supply may affect controller and I/O operation, potentially stopping dependent machinery or production processes.
Check the incoming DC source, wiring, chassis connections and installed modules. A rack fault does not automatically mean the power supply has failed.
Match the exact 1756-PB72 catalog number and verify the chassis, input voltage, module load and installed configuration. This model is not specified for a redundant power-supply configuration. Similar-looking part numbers are not automatically interchangeable.
Send your part and delivery details to AMIKON for availability, pricing and order options.
Inspection or testing scope is confirmed with the quotation. Item condition and procedures are not assumed unless specified in writing.
Packaging, dispatch schedule and estimated delivery are confirmed for each order.
Report damaged, incorrect or non-operational items promptly with order details and supporting evidence. Return authorization and remedies follow the agreed terms.
12 months, subject to quotation terms. Coverage, exclusions and remedies for verified defects are governed by the order agreement.
The nominal input is 24V DC, with a published operating range of 19–32V DC. Verify the incoming supply and polarity before commissioning.
The listed outputs are 5.1V DC at 10.0A, 3.3V DC at 4.0A, 1.2V DC at 1.5A and 24V DC at 2.8A. Maximum total output power is 75W.
No. This model is not specified for a redundant power-supply configuration. Confirm the required system architecture before choosing an alternative.