P-HA-RPS-300000
ABB Harmony MPS III Power Hardware
An ABB Harmony MPS III power-supply assembly for cabinet maintenance, replacement planning and legacy system support.
P-HA-RPS-300000 is an ABB Harmony Modular Power System III power-supply assembly for use within a configured MPS III cabinet. It operates as part of the cabinet power architecture together with the installed power chassis, power entry panel, distribution and monitoring hardware.
For maintenance replacement, match the complete ABB nameplate, installed chassis and electrical requirements before ordering. MPS III power supplies are configuration-specific, so the input, output and redundancy arrangement must agree with the existing system.
| Part number | P-HA-RPS-300000 |
|---|---|
| Product type | ABB Harmony MPS III power-supply tray |
| Power chassis capacity | One or two plug-in power-supply trays |
| Accepted tray inputs | 120/240 VAC and 125 VDC |
| Power configuration | System power, field power, or a combination, according to the installed tray configuration |
| Redundant operation | A second identical tray can provide load sharing and backup capacity |
| Monitoring | System- and field-power voltage monitoring with failure alarm |
| Service features | Local status indication, disconnects and plug-in cable assemblies for fault isolation and replacement |
| Cabinet temperature design | Up to 70 °C inside the cabinet |
Provide every character from the ABB article label, including leading zeros and suffixes.
Identify the MPS III chassis and power-entry-panel article numbers.
Photograph the voltage/current legend and note the connected system and field-power buses.
State the installed supply count, feed arrangement and required load margin.
A clear nameplate photo and the installed chassis details are the primary references for quotation and compatibility checking.
Used when an installed MPS III supply requires a like-for-like maintenance spare and the complete article identity must be preserved.
Check the affected output, source feed, disconnects, downstream wiring and distribution path before declaring the supply failed.
Inspect the system fan, filter and cabinet airflow together with the supply and monitoring indications.
A cabinet may remain online after one power path is lost while operating without the intended reserve capacity.
Confirm the nameplate ratings and connected buses; mechanical similarity alone does not establish electrical compatibility.
A maintenance plan may also require the matching chassis, PEP, fan, monitoring, distribution and mounting hardware.
The service terms below are Amikon commercial support and are separate from ABB technical documentation.
Incoming identity and condition checks; functional or power checks are applied where the part and available fixture allow. The agreed scope can be stated on the quotation.
Protective industrial packing appropriate to the item. Report any dead-on-arrival issue promptly with label, package and installation evidence.
Returns require prior RMA approval and condition review. Warranty term and coverage are confirmed on the quotation; after-sales support assists with claim evidence and part verification.
These part numbers are independent purchasing references only. They are not replacements for the product on this page. Compatibility and stock must be confirmed separately for each item.
It is used within an ABB Harmony MPS III cabinet power system together with the matching chassis, power entry, distribution and monitoring hardware.
Use the voltage and current values on the installed ABB nameplate. Exact input and output ratings are not available for this part number on the current product record.
Send clear images of the complete article label, voltage/current legend, front connectors, chassis label and power entry panel label.
No. Confirm the complete label, connector arrangement, chassis and electrical data before replacement.
Check source feeds, disconnects, supply and bus status, fan/cabinet temperature, output load, chassis identity and redundancy margin.
Provide the exact part number, quantity, destination, required date, machine/system model, nameplate photos, chassis/PEP numbers and installed supply configuration.
For a faster technical and commercial check, send the installed-part details before the requested ship date.
Email Miya ZhengSend your inquiry directly to us