logo
Home > Products > Honeywell Controller >
Honeywell DC-TAOX51 51307717-175 I/O termination assembly

Honeywell DC-TAOX51 51307717-175 I/O termination assembly

DC-TAOX51 51307717-175

DC-TAOX51 6-INCH

DC-TAOX51 Series C

Place of Origin:

USA

Brand Name:

Honeywell

Model Number:

DC-TAOX51 51307717-175

Contact Us
Request A Quote
Product Details
Highlight:

DC-TAOX51 51307717-175

,

DC-TAOX51 6-INCH

,

DC-TAOX51 Series C

Payment & Shipping Terms
Minimum Order Quantity
1
Packaging Details
Brand new and original
Delivery Time
2-3 work days
Payment Terms
T/T
Supply Ability
in Stock
Product Description
HONEYWELL · SERIES C I/O ANALOG OUTPUT IOTA
6-INCH · NON-REDUNDANT

DC-TAOX51

51307717-175

I/O termination assembly for Series C high-level analog output, supporting HART or non-HART operation according to the installed I/O module.

6 in
ASSEMBLY FORM
16
AO CHANNELS
4–20 mA
OUTPUT
Single
NON-REDUNDANT
Confirm the IOTA suffix, I/O module and cabinet arrangement
Sales Manager: Miya Zheng
✉ EMAIL ◉ WHATSAPP
SIGNAL PATH

From controller demand to field current

⌁
Control strategy
Output command
→
▦
DC-TAOX51
Termination assembly
→
◎
Field loop
4–20 mA device
The IOTA provides the field termination layer; output generation, diagnostics and HART capability are determined by the installed Series C I/O module.
I/O PAIRING

One IOTA, two output roles

The installed I/O module sets the communication capability of each output channel.

H CC-PAOH51
High-level analog output with HART
SMART LOOP
A CC-PAON01
High-level analog output, non-HART
CURRENT LOOP
OPERATING ENVELOPE

Loop behavior that affects replacement work

Directly settable current 0 mA or 2.9–21.1 mA
Maximum resistive load 800 Ω at 22–28 Vdc supply
Compliance / open circuit 16 V maximum / 22 V maximum
Settling response Within 1% in 80 ms
Calibrated accuracy at 25 °C ±0.35% of full scale, including linearity
AMIKON · GLOBAL INDUSTRIAL SUPPORT

Keep critical automation requirements moving

Twenty years of industrial automation experience, responsive service and urgent dispatch support for difficult requirements.

PLC DCS HMI VFD
BUYER FAQ

Compatibility questions that protect the retrofit

Q ◇ Can DC-TAOX51 51307717-175 serve both HART and non-HART output modules? A ● Yes. It is paired with CC-PAOH51 for HART output or CC-PAON01 for non-HART output, according to the installed Series C arrangement.
Q ◇ Why is DC-TAOX51 51307717-175 not a direct substitute for DC-TAOX61? A ● DC-TAOX51 is a 6-inch non-redundant IOTA; DC-TAOX61 is the 12-inch redundant form. Their footprint and redundancy architecture differ.
Q ◇ How does DC-TAOX51 51307717-175 behave if control is lost? A ● The associated I/O module can hold the last value or shed each channel to a configured safe value. An electronics failure drives the output toward zero.
Q ◇ Which diagnostics separate field-loop trouble from module trouble on DC-TAOX51 51307717-175? A ● Output readback, discrepancy alarming and open-wire detection help distinguish commanded-current mismatch from a disconnected or high-resistance loop.
Q ◇ What loop budget should be retained with DC-TAOX51 51307717-175? A ● Keep total resistive load within 800 Ω at 22–28 Vdc and account for cable, barriers and the receiving device within the 16 V compliance limit.

Recommended Models

Related industrial automation choices
GTSH2S50PT 592-EEDC NS5-SQ10B-V2 140SDI95300S
PPBE0622 AEC-MOD-CPU1 TBUP535-EA56-AB10 M7555B-01
MBM-M210000 3500/33 149992-04 TA402A ADV551-P60
CRS60 6749 P01120947-F407 PM850UMG PM8RDA HIMA F3421
130B2444 Profometer5 WAVES-HD-8020C-LRU PGM7600
VT505W000000039 GC3000 GLASS-CHEK S10010 MS7510B2007 MS8120A1007
MP-B10-W 6502435 GTD-2000Ex