IS420YDOAS1B is the discrete output I/O Pack used in the Mark VIeS relay contact output module. It interfaces Mark VIeS Safety control logic with discrete process actuators through a compatible relay output terminal board.
SYSTEM FUNCTION
12 DO
Relay output architecture for discrete process control.
02 / CONTROL ARCHITECTURE
A Two-Part Output Module
▦
YDOA I/O Pack
IS420YDOAS1B
›
▤
Relay Terminal Board
SRLY / TRLY
›
◉
Field Actuators
Discrete devices
The complete relay contact output module consists of two orderable parts: the discrete output I/O Pack and the relay contact output terminal board. Terminal board selection determines contact arrangement, wiring and redundancy configuration.
03 / HARDWARE SPECIFICATIONS
IS420YDOAS1B at a Glance
Item
Specification
Manufacturer
GE
Part number
IS420YDOAS1B
Product type
Discrete output I/O Pack
Platform
Mark VIeS Functional Safety System
Output architecture
12 discrete relay output channels
I/O Pack control power
24 / 28 V DC, 19.8 W max.
Power connector
Micro Mate-N-Lok receptacle, AMP 1445022-3
Construction
Aluminum case
Health indication
Visual status LEDs and circuit health variables
Operating temperature
-40 to 70°C (terminal module specification)
The control power and operating temperature are stated for the Mark VIeS relay output module configuration.
04 / TERMINAL BOARD CONFIGURATION
Choose the Correct Relay Arrangement
SIMPLEX
IS410SRLYS2A
12 Form-C relay output circuits through 48 customer terminals. One YDOA I/O Pack is used.
12 DO · Form-C
SIMPLEX / TMR
IS410TRLYS1B
Relay output with coil sensing and integrity feedback. One or three YDOA packs depending on configuration.
12 DO · Form-C
SOLENOID INTEGRITY
IS410TRLYS1D
Six normally open relay outputs with load integrity monitoring.
6 NO · Solenoid sensing
TMR CONTACT VOTING
IS410TRLYS1F / S2F
TMR voted contacts: 12 NO Form-A or 12 NC Form-B, depending on board variant.
3 YDOA packs · TMR
The I/O Pack is ordered separately from its terminal board. Confirm the terminal board suffix and redundancy arrangement before replacement.
05 / CONTACT RATINGS
Ratings Depend on the Terminal Board
Terminal board
Contact rating
IS410SRLYS2A
0.6 A at 125 V DC; 1.2 A at 48 V DC; 2.25 A at 24 V DC; 2.25 A at 120 / 240 V AC
IS410TRLYS1B
0.6 A at 125 V DC; 1.2 A at 48 V DC; 8 A at 24 V DC; 3 A at 120 / 240 V AC
IS410TRLYS1D
0.5 A at 125 V DC; 2.25 A at 24 V DC
IS410TRLYS1F / S2F
2.25 A at 24 V DC
These are terminal-board contact ratings, not a universal standalone rating for IS420YDOAS1B.
06 / DIAGNOSTICS & SYSTEM HEALTH
Output Status Beyond the Command
◉
Power-up Self Test
Checks the I/O Pack during system startup.
▥
Pack Health
Visual status LEDs and health variables available to control logic.
⇄
Command / Feedback Check
Relay output feedback can be checked against the commanded state on compatible configurations.
⌁
Fuse & Wetting Diagnostics
Detection functions depend on the selected terminal board and daughterboard arrangement.
07 / FAQ
Questions Before Ordering
Q1. Can IS420YDOAS1B be used with both SRLY and TRLY terminal boards?
A. Yes. The Mark VIeS relay contact output architecture uses the same YDOA I/O Pack with compatible SRLY and TRLY terminal board options. The board selection determines the output contact arrangement, redundancy and field wiring configuration.
Q2. Why might an IS420YDOAS1B replacement require three I/O Packs instead of one?
A. The quantity depends on the selected terminal board and system redundancy. Simplex configurations use one pack, while TMR configurations can use three packs. Some terminal board variants specify three packs for TMR contact voting.
Q3. Does IS420YDOAS1B provide the same relay contact rating with every terminal board?
A. No. Contact ratings vary by terminal board. For example, SRLYS2A and TRLYS1B have different DC and AC ratings, while TRLYS1D and the TMR voted-contact versions have their own limits. Verify the exact board part number and load before connecting field devices.
Q4. What does the solenoid integrity feature mean when IS420YDOAS1B is installed on IS410TRLYS1D?
A. The TRLYS1D arrangement supports solenoid integrity sensing. It measures solenoid resistance to help detect open- and short-circuit conditions. This is a terminal-board configuration feature, not a general capability to assume for every YDOA installation.
Q5. What should be checked if IS420YDOAS1B reports healthy but the commanded field output is incorrect?
A. Check the output command, terminal board compatibility, relay feedback, field wiring, contact wetting supply and fuse arrangement where fitted. A healthy I/O Pack indication does not by itself confirm that the external field circuit is operating correctly.
GE IS420YDOAS1B / ENQUIRY
Match the Pack to Your System
Send the terminal board number, I/O Pack revision, redundancy type and quantity for a replacement enquiry.
Long-term cooperation for industrial automation needs.
Founded in Hong Kong in 2005, AMIKON is a global supplier of industrial automation parts and control system components. Over the past two decades, our team has continued to expand its product range and customer network.
Our inventory covers a broad selection of industrial automation spare parts, including PLC, HMI, DCS, panel controllers, industrial PCs and VFD components.
Can't find your exact part number? Our experienced sales and customer service team is ready to help with hard-to-find parts and complex spare-parts requirements. We work to help keep your production running.
09 / RECOMMENDED MODELS
More Industrial Automation Parts
MCX15B2V 080G0284
330130-030-12-05
QRA55.C27
TDS3052
3500/25_SIL2
CE250A
CW240
80025-523-15-R
AV3255DN-H
FTC-1045
EY-IO551F001
PDL4335
KIT-CBG12-1-PF
EL-4KM-V44
PGM7600
NS5-SQ10B-V2
gSC2 PN:10002757
PW481 SPW481-13
HCAB060000041
SDV144-S13
LNL-3300
ISMA-B-AAC20-LCD
V200-18-E2B
LT-800-072-03
600 3G/HD
ESG 160/90
IN1606
EVZS8O4MM-BI
IC693PWR322K
662-698 MHz-M1
MC-3-ASF-100
HIMA F3421
40071361981
GTSH2S50PT
PM850UMG PM8RDA
380011-0200
972972-003
XI582B-EU
PN:10002757
MP-B10-W 6502435
More Popular Models
Discover more industrial automation products and spare parts.