HONEYWELL / CSN SERIES
CSNK500M-600
Closed-Loop Current Sensor
Galvanically isolated measurement of AC, DC and pulsed current for drive feedback, protection and current-control duties.
|
→
PRIMARY
|
| 500 A.t rms Nominal current |
100 mA Nominal output |
1 : 5000 Turns ratio |
DC to 100 kHz Bandwidth |
|
01 / OVERVIEW
Measure current without opening the primary circuit.
|
The primary conductor passes through the central aperture. A magnetic compensation circuit develops a secondary current proportional to the primary ampere-turns, maintaining electrical isolation between the high-current conductor and the measurement electronics.
The sensor supports bidirectional DC, alternating current and impulse current with rapid response and a broad frequency range.
|
| AC and DC measurement One sensor covers steady and changing current. |
High electrical isolation Primary and secondary circuits remain separated. |
Fast dynamic response Suitable for control and protection loops. |
| CURRENT RANGE | |
| Nominal primary current | 500 A.t rms |
| Continuous measuring range | 0 to +/-1200 A.t |
| AC peak range | 0 to +/-1275 A.t |
| OUTPUT AND SUPPLY | |
| Nominal output at 500 A.t | 100 mA |
| Supply voltage | +/-15 to +/-18 Vdc |
| Current consumption | 20 mA plus output current |
| ACCURACY AND SPEED | |
| Accuracy at 25 degrees C | Maximum +/-0.5% of nominal current |
| Linearity | Better than +/-0.1% |
| Response time | Better than 1 microsecond |
| Bandwidth | DC to 100 kHz |
| ENVIRONMENT AND CONNECTION | |
| Isolation test | 6 kV rms, 50 Hz, 1 minute |
| Operating temperature | -40 to +85 degrees C |
| Connector for suffix -600 | RSD-46607-001 |
|
03 / SENSING LOOP
Ampere-turns define the effective range.
|
A single conductor pass gives one primary turn. Additional passes multiply the effective ampere-turn value and reduce the conductor current required to reach the same secondary output. |
|
1 pass
PRIMARY CONDUCTOR
500 A = 500 A.t |
⟷ |
2 passes
PRIMARY CONDUCTOR
250 A = 500 A.t |
| 01 | Can CSNK500M-600 replace a standard CSNK500M directly? | The electrical ratio is shared, but suffix -600 uses connector RSD-46607-001. Confirm the harness and pin orientation. |
| 02 | How do additional conductor passes affect CSNK500M-600? | Each aperture pass adds one primary turn. Two passes produce 500 A.t from 250 A of conductor current. |
| 03 | Which burden can CSNK500M-600 drive at 1275 A.t peak? | At a +/-18 V supply, keep the measuring resistance at 5 ohm maximum at the AC peak limit. |
| 04 | Can CSNK500M-600 measure bidirectional DC? | Yes. Secondary-current polarity follows the direction of the primary current, supporting positive and negative DC. |
| 05 | What can alter CSNK500M-600 accuracy after replacement? | Supply imbalance, excessive burden, connector polarity, residual offset and conductor placement should be checked during validation. |
| FR-2RU-10-2 | J120-361 | XF830A | GI357.Z53 |
| CP40000000 | MI-585162-2 DI-9001 | ADV551-P50 | 72752-01K |
| BMXCPS3020H | MS-UD650 | 868-1-20 | S1BB4D-06 |
| PCO3000BL0 Rev.2.011 | 5R4D11A | 703-1178 | MV1417 |
| TAP-601-AAAA | FVR46 | 04079200 | LSC-X21-02M |
| Z043.584/02 | 300E | POWTOR0002 | AAI143-H53 |
| GW 90821 | 031-01095-002 | SGDV-5R4D11A | PCO3000BL0 |
| IC200UDR005-BG | 5073523EQ | inBio260 | S4000T/31180-2 |
| SAI143-S03 | JASP-WRCA01B | MMI20013514 | uh50-g36c-ae00-f |
| OEE-1 | Z035.263/04 | ADV551-P50 | PCO3000BL0 Rev.2.011 |
|
CONNECTOR / SUPPLY / BURDEN
Request CSNK500M-600 AvailabilitySales Manager: Miya Zheng |
sales@amikon.cn WhatsApp: 86-18020776792 |
Send your inquiry directly to us