CC-PDIH01 is a 32-channel Series C high-voltage digital input module used with dedicated IOTAs for 120 V AC, 125 V DC, proximity or 240/250 V AC field signals.
Type
High-voltage digital input
System
Experion PKS Series C I/O
Focus
32 × AC/DC inputs
Brand
Honeywell
Official data
Technical Specifications
Select a group to view its verified specifications.
View 6 module specifications ›
Input channels
32
Signal families
120 V AC, 125 V DC, 120 V AC proximity and 240/250 V AC
Input logic
Direct or reverse
Isolation method
Galvanic / optical
Isolation withstand
1500 V AC rms or ±1500 V DC
Redundancy
Optional with supported IOTAs; not documented for CC-TDI151
View 5 IOTA selection specifications ›
CC-TDI110
9-inch non-redundant IOTA for 120 V AC / 125 V DC; 90–132 V AC or 100–138 V DC
CC-TDI120
12-inch redundant IOTA for 120 V AC / 125 V DC; 90–132 V AC or 100–138 V DC
CC-TDI151
12-inch non-redundant IOTA for 120 V AC proximity inputs; 90–132 V AC
CC-TDI220
9-inch non-redundant IOTA for 240/250 V AC; 180–264 V AC
CC-TDI230
12-inch redundant IOTA for 240/250 V AC; 180–264 V AC
Officially documented
Compatibility & Replacement
Unconfirmed substitutions and migration assumptions are excluded.
IOTA determines the field-voltage class
Honeywell uses the same CC-PDIH01 IOM with different IOTAs for the documented voltage and redundancy arrangements. The installed IOTA part number must be matched exactly; voltage class and redundancy cannot be inferred from the IOM alone.
Field context
Applications & Fault Scenarios
Scan the symptom, first check and operational risk.
!
01Motor or breaker status
Observe
The input is stuck or opposite to the field state.
Check
Check field voltage, IOTA and direct/reverse logic.
Risk
A sequence or permissive may be blocked.
↔
02Proximity input service
Observe
A state is absent after hardware work.
Check
Identify the IOTA and verify its documented voltage class.
Risk
The wrong spare or test method extends downtime.
⌁
03Redundant input maintenance
Observe
Redundancy is alarmed although states remain visible.
Check
Confirm both positions, IOTA type and system diagnostics.
Risk
Operational risk rises until redundancy is restored.
Commercial service
About Amikon & Service
Order review, inspection, dispatch and after-sales support in one concise service flow.
Amikon commercial serviceSeparate from manufacturer technical data
Customer meeting at AmikonConnection and functional review
01
Order Review
Part number, quantity and system context confirmed.
02
Inspection & Testing
Condition and available checks recorded.
03
Packing & Dispatch
Protective packing prepared for the destination.
DOA
Prompt report with evidence.
Returns
Prior authorization required.
Warranty
Terms stated in the quotation.
After-sales
Order-based follow-up support.
RFQ checklist
Send five order details
Enough information to review the request without assuming compatibility.
Part Number
Quantity
Destination
Required Date
Machine / System Model
Independent sourcing references
Multi-brand Spare Parts Also Requested
Thirty models selected from the supplied reference list for independent sourcing enquiries.
These models are independent procurement references only and are not substitutes for CC-PDIH01. Compatibility, configuration and inventory must be confirmed separately for each request.
A105 2155
022363671
022363450
800FM-MT44
TB20H100
6219-0068
5212ZZTNC3
25B-35B-60B-80B-AL800, 09789G048
CG907A3
CS5F-100
V61R517A-A213JB
60313995
6310 2ZJEM
RSC-22 RSC-M048
777R-017
FAZ-C2/1-NA
HMCP003A0C
153SA43AM000058
SK25-20
1275225
FS1464 T20IP/4.7lb-ft RK242-SET DCLNL205D
SFF4,H1863
HC-4E
152SA400E
FP-728
A097247
176C663G01
800F-15YE112
M061-FC08
92004845-1
Six buyer questions for CC-PDIH01
FAQ
Procurement, replacement and fault questions specific to this exact part number.
Why is the IOTA part number essential when ordering Honeywell CC-PDIH01? ›
CC-PDIH01 is used with different high-voltage IOTAs. The IOTA determines the documented 120 V AC, 125 V DC, proximity or 240/250 V AC field service and the redundancy arrangement.
Can Honeywell CC-PDIH01 use the CC-TDI151 proximity IOTA redundantly? ›
No. Honeywell documents the CC-TDI151 proximity arrangement as non-redundant; redundancy is available only with the supported redundant IOTAs.
What should be checked when a Honeywell CC-PDIH01 input remains stuck? ›
Verify the actual field voltage, terminal wiring, IOTA voltage class and configured direct or reverse logic before replacing the 32-channel IOM.
Can Honeywell CC-PDIH01 accept both 120 V AC and 125 V DC with the same termination? ›
Do not infer that from the IOM number. The applicable IOTA defines the field-voltage class, so the complete IOTA part number must be matched.
What isolation level is documented for Honeywell CC-PDIH01? ›
Honeywell specifies galvanic and optical isolation with 1500 V AC rms or ±1500 V DC dielectric withstand.
Which details are needed for a Honeywell CC-PDIH01 replacement quote? ›
Provide both IOM and IOTA part numbers, field voltage and input type, redundancy requirement, Experion release, quantity, destination and required date.