AMIKON LIMITED
We'll get back to you as soon as possible.
Place of Origin:
USA
Brand Name:
General Electric
Model Number:
IC200PNS001
| Function Area | Description |
|---|---|
| PROFINET Interface | Implements distributed I/O, Version 2.2 Class A |
| Compatibility | Works with VersaMax series, RX3i and RX7i PLCs |
| Ports | Two RJ45 ports, embedded switch, supports linear, star, and ring topologies |
| Diagnostic Data | 32 input status bits, 32 output control bits |
| Remote I/O Support | Up to 8 VersaMax I/O modules or carriers per instance |
| Power Consumption | 5 VDC backplane, 3 W typical |
| Transmission | 10/100 Mbps, max 100 m per segment, extendable with switches or fiber converters |
| Firmware Upgrade | USB port for firmware updates; requires RX3i CPU ≥7.0 and Proficy ME ≥7.0 |
| I/O Coordination | Retrieves input data and delivers output data for remote node |
| Alarms & Diagnostics | PROFINET alarms, fault reporting, module status monitoring |
| Hot Swap | Replacement of de-energized excessive power supply supported |
| Network Management | Module scanning, configuration, communication with I/O controllers, publishes remote I/O data |
| Environmental | Operating temperature 0-60 °C, no fan required |