Product Model:
IMDSO14
Product Parameters:
Digital Output Slave
Country Of Origin:
SWEDEN
Place Of Shipment:
Xiamen, China
Estimated Shipping Size:
3.7x31.7x17.8cm
Manufacturer:
ABB
Weight:
0.2 Kg
Warranty:
12 Months
Highlight:

16 Output Points Digital Output Module

,

24 VDC Compatibility DSO Module

,

INFI 90 OPEN System INFI 90 Module

Payment & Shipping Terms
Minimum Order Quantity
1
Price
66USD
Packaging Details
Brand new and original
Delivery Time
2-3 work days
Payment Terms
T/T
Supply Ability
in stock
Product Description
Product Details 
The ABB IMDSO14 Digital Output module (DSO) is designed to interface the INFI 90 OPEN Strategic Process Management System with industrial processes, providing reliable digital output signals to control field devices. With 16 output points, the module ensures precise digital switching (ON/OFF) for connected equipment, supporting critical process control tasks in demanding industrial environments.
Engineered as a digital output slave, the IMDSO14 enables seamless communication between control modules and field devices. It translates control commands from the INFI 90 system into actionable signals, ensuring accurate and timely operation of valves, actuators, and other digital equipment. The module's compatibility with 24 VDC systems allows for integration into a wide range of process control architectures.
The IMDSO14 remains a valuable replacement or spare part for legacy INFI 90 installations. Compact and lightweight, it provides robust performance while maintaining ease of installation and long-term reliability. This module is ideal for facilities requiring continuity of service without costly system overhauls.
Specifications
Property Characteristic/Value
Power requirements
Voltage 5 VDC (±5%)
Current 275 mA (typical)
370 mA (maximum)
Dissipation (logic only) 1.375 W (typical)
1.850 W (maximum)
Overvoltage category on outputs II, per IEC 1010-1
Outputs 16 digital
Load voltage 24 VDC, 48 VDC
Load current (maximum) 250 mA (24 VDC), 125 mA (48 VDC)
Off leakage current (maximum) 10 µA at 70°C (158°F)
On voltage drop (maximum) 2 V at 70°C (158°F)
Current consumption 150 mA (typical), 250 mA (maximum) per output at 24 VDC
75 mA (typical), 125 mA (maximum) per output at 48 VDC
Installation & Static Safety Guidelines
ABB IMDSO14 Digital Output Module with 16 Output Points 24 VDC Compatibility for INFI 90 OPEN System 0
  • Use a Static Grounding Wrist Strap
    Always wear a grounded wrist strap when installing or removing modules. Static discharge can damage sensitive devices within the module. Ensure all equipment and work surfaces are grounded.
  • Keep Modules in Static Shielding Bags
    Store the module in its static shielding bag until installation. Retain the bag for future use to protect the module from electrostatic discharge.
  • Ground Bags Before Opening
    Touch the bag containing the module to grounded equipment or housing before opening to equalize electrical charges.
  • Handle by the Edges
    Avoid touching circuit boards and components directly. Always handle assemblies by the edges to minimize static exposure.
  • Ensure Proper Grounding of Connected Devices
    Verify that all devices connected to the module are properly grounded before powering the system.
  • Ground Test Equipment
    Ensure all testing tools and instruments are properly grounded before use.
  • Use an Antistatic Field Service Vacuum
    If necessary, remove dust from cards with a grounded, antistatic vacuum to prevent static damage.
  • Do Not Use Lead Pencils for DIP Switches
    Avoid setting DIP switches with lead pencils. Contact contamination can cause malfunctions on the circuit board.
  • Set Module Address Prior to Installation
    Configure the module S1 address switch before inserting it into the system.
  • Configure Termination Units or Modules
    Properly configure the Termination Unit (TU) or Termination Module (TM) to output digital signals from the DSO to connected field devices.
Why Choose Amikon for Industrial Automation Parts
Timeliness
Minimize disruptions, reduce maintenance downtime, and keep your operations running smoothly. Our fast response and global shipping ensure you get the parts you need, exactly when you need them.
Diversity
We specialize in sourcing industrial automation components that are no longer available from the original manufacturer. From PLCs and HMIs to DCS modules and rare legacy parts, we provide solutions for even the most hard-to-find items.
Reliability
As a trusted supplier for over 20 years, Amikon delivers new surplus industrial automation parts to businesses of all sizes. Our proven track record ensures high-quality products, competitive pricing, and exceptional customer service.

Contact Our Expert
Miya Zheng - Sales Manager
Phone / WhatsApp: +86-18020776792
Partner with us and keep your industrial systems running efficiently and reliably.

Send your inquiry directly to us