Модуль Safety Manager 24 VDC, объединяющий удаленное выполнение логики с 32 программно конфигурируемыми безопасными каналами ввода-вывода.
32 CHANNELS
24 VDC SUPPLY
SM PLATFORM
01 · PURPOSE
Move safety logic closer to field I/O
FC-RUSLS-3224 is a conformal-coated remote universal logic solver for Honeywell Safety Manager. Each channel is assigned in software for a supported safe digital or analog duty, while the module executes the approved remote safety logic.
The hardware role and the validated application belong together. A physical replacement alone does not complete safety restoration.
02 · TECHNICAL LEDGER
Operating limits and channel capacity
01
Supply voltage
24 VDC, -15% to +30%
02
Module current
300 mA maximum without field load
03
Universal channels
32, software configurable
04
Input allocation
Up to 32 DI or AI; up to 1 ESD input
05
Output allocation
Up to 32 DO; up to 16 AO
06
Combined DO load
9 A maximum
07
Ambient range
-40°C to +70°C outside module
08
Relative humidity
10% to 95%, non-condensing
03 · 32-CHANNEL FUNCTION BAND
One hardware base, five safety duties
DI DIGITAL INPUT
ESD SHUTDOWN INPUT
AI ANALOG INPUT
DO DIGITAL OUTPUT
AO ANALOG OUTPUT
Supported line monitoring, scaling, diagnostics and safe-state behavior are configured per application. Channel allocation must remain within the module limits.
04 · SYSTEM PATH
From field signal to safe action
⇄
Field
Sensors, shutdown devices and actuators
IOTA
Termination and module interface
RUSLS
Safe I/O processing and remote logic
Action
Validated trip, permissive or controlled response
05 · COMMISSIONING SEQUENCE
Hardware first, proof testing last
01 Install on matched IOTA
02 Restore earth and 24 VDC
03 Load approved configuration
04 Prove every safety function
06 · PRODUCT FAMILY
Modules that share the remote I/O architecture
FC-RUSLS-3224 Safe I/O + remote logic
FC-RUSIO-3224 Universal safe I/O
FC-IOTA-R24 Termination assembly
FC-MCAR-02 36-inch carrier
Executes local logic
No RUSLS logic role
Field wiring base
Mechanical and power base
AMIKON · SINCE 2005
Support for complex automation spare needs
Amikon supports PLC, HMI, DCS, panel control, industrial PC and VFD spares for customers worldwide.
Our experienced team assists with difficult part codes and maintenance requirements.
sales@amikon.cn WhatsApp: 86-18020776792
07 · BUYER FAQ
Safety lifecycle questions
01
Can Honeywell FC-RUSLS-3224 mix input and output types?
Yes, within the supported channel and load limits defined by the validated application.
02
How does Honeywell FC-RUSLS-3224 differ from FC-RUSIO-3224?
RUSLS combines universal safe I/O with remote logic; RUSIO provides the universal safe I/O role.
03
Why must Honeywell FC-RUSLS-3224 revision be checked?
Diagnostics and lifecycle actions can be revision-specific, so installed and offered revisions must be compared.
04
Can Honeywell FC-RUSLS-3224 DO capacity be judged per channel?
No. The combined digital-output load must also remain at or below 9 A.
05
What completes Honeywell FC-RUSLS-3224 commissioning?
Proof of every channel, diagnostic, communication path, safe state and shutdown response.