AMIKON LIMITED
हम जितनी जल्दी हो सके आप के लिए वापस आ जाएगा.
उत्पत्ति के प्लेस:
यूएसए
ब्रांड नाम:
Bently Nevada
मॉडल संख्या:
133396-01
| Category | Specification Details |
|---|---|
| Product Name | Overspeed Detection I/O Module |
| Part Number | 133396-01 |
| System Compatibility | Bently Nevada 3500 Series Machinery Protection System |
| Associated Front Cards | 3500/53 Electronic Overspeed Detection System |
| Number of Channels | 2 Independent Channels (Overspeed Detection) |
| Input Type | Proximity Transducers / Magnetic Pickups |
| Power Consumption | 8.0 Watts (Typical) |
| Recorder Output | +4 to +20 mA (Proportional to Speed) |
| Input Impedance | 20 kΩ (Standard) |
| Speed Range | Up to 100,000 RPM |
| Accuracy | Within ±0.1% of Full Scale |
| Voting Logic | Supports 2-out-of-2 or 2-out-of-3 configurations |
| Standard Compliance | API 670, API 612 (Machinery Protection Standards) |
| Operating Temp | -30°C to +65°C (-22°F to +149°F) |
| Storage Temp | -40°C to +85°C (-40°F to +185°F) |
| Humidity | 95% Non-condensing |
| Mounting | Rear Rack Mount (Full-height) |
Contact: Miya Zheng
Email: sales@amikon.cn
WhatsApp: +86 180 2077 6792
In the Bently Nevada 133396-01 setup, the main job is overspeed detection. It works with the 3500/53 monitor card and reacts when rotational speed becomes unsafe. In practice, it’s part of the layer that helps protect critical rotating equipment, especially where fast response is needed.
It supports both Passive Magnetic Pickups (MPUs) and Proximitor sensors.
That gives some flexibility in the field, since different turbine or compressor setups may use different speed measurement methods.
In real applications, multiple 133396-01 modules can be arranged in a redundant configuration. This allows 2-out-of-2 or 2-out-of-3 (2oo3) voting logic to be implemented.
The idea is fairly simple — reduce false trips, but still keep the protection reliable enough for critical machinery safety.
Yes, it’s typically used in systems that follow API 670 and API 612 requirements.
In turbine overspeed protection systems, this kind of compliance is basically expected, especially in power generation and oil & gas projects.
Yes. Each channel provides a 4-20 mA output, which can be sent to DCS or PLC systems.
This is often used for remote monitoring, trending, or integrating speed data into broader plant control systems.